Battery runtime

Estimate backup time from battery energy, load and conversion losses.

About this tool

Enter measured output power in W, not the UPS rating in VA. Wh is energy. For identical batteries, series adds voltage and parallel strings add Ah; the Wh mode already describes the entire bank.

Energy estimate: usable Wh ÷ (load W ÷ efficiency + extra idle W). The usable fraction is the energy available from the present charge down to your chosen cutoff. Additional idle power is battery-side consumption; set it to zero if already included in efficiency. Without load or idle draw the model has no discharge, but a real battery still has losses.

Optional Peukert comparison uses the battery’s rated Ah, rated discharge duration H and manufacturer exponent k: Iᵣ = Ah/H; time = H × (Iᵣ/I)^k × usable fraction. At k = 1 it equals the energy estimate. At higher current than Iᵣ, k > 1 reduces time; below Iᵣ it increases it. Use datasheet values within their measured range. The sample k is illustrative.

Both estimates assume constant voltage, load and efficiency. The usable fraction scales Peukert time linearly. Temperature, aging, self-discharge, shutdown voltage and actual UPS runtime curves are not modeled; this does not verify the UPS power rating or predict a specific device’s backup time.